This shows you the differences between two versions of the page.
Both sides previous revision Previous revision Next revision | Previous revision Next revision Both sides next revision | ||
chara:trouble_shooting [2022/02/09 19:24] charaobs |
chara:trouble_shooting [2023/02/08 19:24] charaobs [The new OPLE system] |
||
---|---|---|---|
Line 18: | Line 18: | ||
* Check the time on the OPLE server. If the time is off or there are any lost ticks/ | * Check the time on the OPLE server. If the time is off or there are any lost ticks/ | ||
* Are the [MAN] buttons pressed (gray) for the moving carts on the OPLE Control gui? (The reference cart will remain green.) | * Are the [MAN] buttons pressed (gray) for the moving carts on the OPLE Control gui? (The reference cart will remain green.) | ||
- | * Check that the carts are within delay line range (-1.3 to 44.25 meters) and errors are small. Were the carts homed and checked before the first slew of the night? Did any carts go to the front switch after slewing? This can cause them to lose their position. | + | * Check that the carts are within delay line range (-1.3 to 44.25 meters) and errors are small. Were the carts homed and checked before the first slew of the night? Did any carts go to the front switch after slewing? This can cause them to lose their position. |
* Are the LDC's working? | * Are the LDC's working? | ||
* Is the glass position within allowable range (-10mm to 49mm) on all beams? | * Is the glass position within allowable range (-10mm to 49mm) on all beams? | ||
Line 26: | Line 26: | ||
* Check the instrument alignment. Is flux getting through to the detector? How long has it been since the last NIRO camera alignment? Classic and CLIMB programs can run for about an hour before the light will drift from the central pixel. Use the Classic or CLIMB gui to view the light on the pixels by clicking the PICTURE tab and then the PIXEL AREA button. Turn the camera off with the STOP button. Is the right dither power turned on? CLIMB 1 and Classic use different dithers. If Classic or CLIMB fringes are found in a scan, but not when in recording mode, the dither powers are likely not on. Are the camera settings correct for the seeing conditions and flux levels? | * Check the instrument alignment. Is flux getting through to the detector? How long has it been since the last NIRO camera alignment? Classic and CLIMB programs can run for about an hour before the light will drift from the central pixel. Use the Classic or CLIMB gui to view the light on the pixels by clicking the PICTURE tab and then the PIXEL AREA button. Turn the camera off with the STOP button. Is the right dither power turned on? CLIMB 1 and Classic use different dithers. If Classic or CLIMB fringes are found in a scan, but not when in recording mode, the dither powers are likely not on. Are the camera settings correct for the seeing conditions and flux levels? | ||
+ | * There is a script that will display offsets for all scopes against Hour Angle to help find offsets when using MIRCX and MYSTIC. You'll need to log into the MIRCX spooler computer with the command ssh spooler@mircx, | ||
===== The new OPLE system ===== | ===== The new OPLE system ===== | ||
Line 35: | Line 36: | ||
If a cart cannot be started, stopped or otherwise commanded, look to the OPLESystem gui to see if a green indicator has turned red. A message will also often pop up on the ople gui saying the command could not be sent. This may require a simple start command to restart the server or a reboot of the computer to get it back to yellow and then a start to get it back to green. Do either of these steps with a right click of the red button and then select start or reboot. After a reboot, select start to load the servers after the indicator has turned yellow. When this is done, the ople server will need to be connected to the newly restarted server. Type " | If a cart cannot be started, stopped or otherwise commanded, look to the OPLESystem gui to see if a green indicator has turned red. A message will also often pop up on the ople gui saying the command could not be sent. This may require a simple start command to restart the server or a reboot of the computer to get it back to yellow and then a start to get it back to green. Do either of these steps with a right click of the red button and then select start or reboot. After a reboot, select start to load the servers after the indicator has turned yellow. When this is done, the ople server will need to be connected to the newly restarted server. Type " | ||
- | Some times a cart is stopped and cannot be commanded. If the cart has gone to the front hard or back hard switch, it will not be usable until it is moved from the switch and the Ople Controller box is reset. There are 6 silver boxes for these controllers with two green LED's for the front and back switches and two red LED's for the back hard and front hard switches. If a red LED is lit, there will be an error displayed on the message window and the cart is disabled. The cart will need to be moved ofo the switch and then the box can be reset with the RESET button on the front. The error display will go away and the red LED will be off. The cart is now controllable. | + | Some times a cart is stopped and cannot be commanded. If the cart has gone to the front hard or back hard switch, it will not be usable until it is moved from the switch and the Ople Controller box is reset. There are 6 silver boxes for these controllers with two green LED's for the front and back switches and two red LED's for the back hard and front hard switches. If a red LED is lit, there will be an error displayed on the message window and the cart is disabled. The cart will need to be moved off the switch and then the box can be reset with the RESET button on the front. The error display will go away and the red LED will be off. The cart is now controllable. |
===== Restarting Servers ===== | ===== Restarting Servers ===== | ||
Line 54: | Line 56: | ||
\\ The Shutters server can become unresponsive or disconnected from the Socket Manager. This server must be restarted from the lab and not from the Control Room. Follow these instructions to restart it. Note that Shutters runs on ople, not ctrscrut. \\ \\ To start the shutter server on ople: \\ \\ Log into the ople computer and kill the process labeled shutters with the PID as described in **Restarting Servers** | \\ The Shutters server can become unresponsive or disconnected from the Socket Manager. This server must be restarted from the lab and not from the Control Room. Follow these instructions to restart it. Note that Shutters runs on ople, not ctrscrut. \\ \\ To start the shutter server on ople: \\ \\ Log into the ople computer and kill the process labeled shutters with the PID as described in **Restarting Servers** | ||
+ | |||
+ | ==== Restarting Socket Manager ==== | ||
+ | |||
+ | In very rare circumstances, | ||
+ | |||
+ | Follow these instructions to restart the socket manager, but only do so if really necessary: | ||
+ | |||
+ | ssh -X observe@ctrscrut | ||
+ | |||
+ | killall socket_manager | ||
+ | |||
+ | socket_manager & | ||
==== MIRC-X CredoneImAcq Server ==== | ==== MIRC-X CredoneImAcq Server ==== | ||
Line 126: | Line 140: | ||
You may have to reinitialize the scope on a bright star. If the powers were turned off quickly when the problem was noticed, the position of the scope should be retained and slewing to a bright star will get it in the finder. If not, you may need to go out to the telescope to find the bright star to reacquire the scope' | You may have to reinitialize the scope on a bright star. If the powers were turned off quickly when the problem was noticed, the position of the scope should be retained and slewing to a bright star will get it in the finder. If not, you may need to go out to the telescope to find the bright star to reacquire the scope' | ||
- | Be aware that when restarting a dome server, the telescopes position may not be retained and the dome gui may display Az: 0.0. El: 0.0. The gui will scroll messages that say Az: 0.0. El: 0.0 with an error in scope position. | + | Be aware that when restarting a dome server, the telescopes position may not be retained and the dome gui may display Az: 0.0. El: 0.0. The gui will scroll messages that say Az: 0.0. El: 0.0 with an error in scope position. If the scope is known to be at STOW position, you can manually enter the scope' |
- | Also be aware that the gains do not always return to the normal values of Slew 4-7 and Tracking 7-10 when a dome server has crashed and is restarted. | + | Also be aware that the gains do not always return to the normal values of Slew 4-7 and Tracking 7-10 when a dome server has crashed and is restarted. They may come up as Gain 22 for all axes and modes and they will need to be turned down or the scopes will oscillate badly. |
==== Telescope is not receiving the commanded position for a target. ==== | ==== Telescope is not receiving the commanded position for a target. ==== | ||
Line 204: | Line 218: | ||
[[: | [[: | ||
+ | |||
+ | ===== LabAO ===== | ||
+ | |||
+ | ==== LabAO Shutters Not Working ==== | ||
+ | |||
+ | If the labao shutters are not working, the power button on each of the two red control boxes on the top of the table might need to be pressed. After that the other button needs to be pressed and held for 5 seconds so that the units can be controlled remotely. (Note: look for instructions on table.) | ||
+ | |||
+ | ==== LabAO DM Electronics ==== | ||
+ | |||
+ | If a labao server complains that it failed to find the EDAC40 device, try unplugging the power and ethernet cables for DM and then replugging in again. | ||
===== OPLE and Metrology ===== | ===== OPLE and Metrology ===== | ||
Line 285: | Line 309: | ||
* If either Phase 1 or Phase 2 states say IDLE for a given VPN, then you need to re-establish the connection. To do this, click on the " | * If either Phase 1 or Phase 2 states say IDLE for a given VPN, then you need to re-establish the connection. To do this, click on the " | ||
* Make sure to close Firefox by using CTRL-Q to quit the program and not just close the window. | * Make sure to close Firefox by using CTRL-Q to quit the program and not just close the window. | ||
+ | |||
+ | ===== Network Problems ===== | ||
+ | |||
+ | ==== User accounts not recognized ==== | ||
+ | |||
+ | The gps computer does the user authentication for the control side while ctrscrut provides the home directories. Yellowpages is gone, the new paradigm is LDAP (local directory access protocol). If you can't log on to computers on the control network, then make sure both ctscrut (michelson) and gps computers are running. If the login screen screen on ctrscrut says " | ||
+ | |||
+ | If gps computer does not start, check the power distribution unit (PDU) at the top of that rack. If any units show both " | ||
===== General Problems ===== | ===== General Problems ===== |