Things Judit had to do in the lab to recover after power outage
Shutters power cycled on the box in the rack
Home Newport stage VIS beams (same as Esp BC2 gui VISB axis)
Bootlaunch on ctrscrut to get the BS servers running
Home Newport all 6 BS stages (guis Esp BS1 and BS2)
Labao DM electronics were all fine, all those UPSes kept the power
Started up labao computer
Pushed power button on the USB hub for labao cameras before starting labao servers so that the servers could find the cameras
Labao shutters were OK, on same UPSes as labao DM
Cycled ApertureWheels power and inited all 6 Aperture Wheels
Started up tiptilt computer → check was forced due to not clean shutdown
Soft rebooted tiptilt computer with entering BIOS and RE-SAVED it for proper clock start
Homed all axes of Titlit zabers (ZABER 2) using ENG gui, because they lost their position. [Best to do this when the beams are aligned with labao and corend cubes are in, so that the movements can be seen in tiptilt gui. Laser ND=6. One click on Home button on any axis homes all axes. After homing, for each axes GO TO SETPOS takes it to the latest position in the cfg file. It is likely that the zaber positions need to be adjusted and fresh set potions saved.]
All pops were out and PERI postions lost → All 6 PERI axes had to be homed and AFTER THAT using set first pop5 with POPPERIGTK and adjusted M10 as needed.
Irimage computer was off → I restarted it, but were unable to log in (it asked for observe pw, but did not accept it) This has to be fixed.
chara/power_recovery.1603994877.txt.gz · Last modified: 2020/10/29 14:07 by gail_stargazer