chara:new_operating_procedures [2024/04/17 07:29]
bflores [Starting the vacuum pump and opening valves]
chara:new_operating_procedures [2024/04/30 00:04]
bflores [Common Issues]
Line 1: Line 1:
 ====== New Operating Procedures ====== ====== New Operating Procedures ======
  
-Last updated 04/17/2024+Last updated 04/22/2024
  
 [[:chara:operating_procedures|Link for Old Operating Procedures Page]] [[:chara:operating_procedures|Link for Old Operating Procedures Page]]
Line 818: Line 818:
         - can use rotation wheel. spica is 90 degrees CW from azimuth of star.         - can use rotation wheel. spica is 90 degrees CW from azimuth of star.
         - use steps 222 - 500 and wait for dm to adjust before clicking again.         - use steps 222 - 500 and wait for dm to adjust before clicking again.
-      - as of 10/13spica requests that telemetry is recorded once data sequence is being recorded. +      - when finishedon ip_det, press **[FTT SERVO] **and** [OFFLOAD]**.
-        - **CD,**  Control tab, next to Star Acquired, **[TELEMETRY]**  (click once, nothing will pop up)+
   - Make sure data acquired line comes in on CD, otherwise do **[DATA ACQ]. **   - Make sure data acquired line comes in on CD, otherwise do **[DATA ACQ]. **
       - or make sure to **[REOPEN]**  CD during shutters       - or make sure to **[REOPEN]**  CD during shutters
Line 1278: Line 1277:
         - if that doesn't work, go to the lab and try giving it a soft nudge to get it unstuck.         - if that doesn't work, go to the lab and try giving it a soft nudge to get it unstuck.
         - if it doesn't move, check that the ribbon and cable are on the track and not caught somewhere. Also check the cable spooler is not loose and wind it up if it is.         - if it doesn't move, check that the ribbon and cable are on the track and not caught somewhere. Also check the cable spooler is not loose and wind it up if it is.
-  - cart error is jumping about 100 microns every 4-6 seconds. +  - cart error is jumping about 100 microns every 4-6 seconds. On mircx/mystic, fringes will show an oscillating pattern that corresponds to the jump in cart error. In the lab, a faint ticking sound may also be heard. 
-      - On mircx/mystic, fringes will show an oscillating pattern that corresponds to the jump in cart error. +      - First try restarting ople server. 
-      - In the lab, a faint ticking sound could also be heard. +        - Turn off the carts 
-      - Turn off the cart +        - Restart ople server 
-      - On Ople System Controller, restart the ople computer for the cart +        - Track carts. 
-      - When its done, rehome and check the cart. Issue should go away.+      - if problem persists, restart ople system controller. 
 +        - On Ople System Controller, restart the ople computer for the cart. 
 +        - When its done, rehome and check the cart. Issue should go away.
  
 === Hut Error === === Hut Error ===
chara/new_operating_procedures.txt · Last modified: 2024/05/15 06:00 by bflores